12. Primary address of module slot 4
The primary address of module slot 4 in MULTICAL® 803 can be adjusted in the SETUP loop. The address can be
selected in the interval 0…250.
13. Averaging period of min./max P and Q
The averaging period used in the calculation of minimum and maximum values of power (P) and flow (Q) can be
adjusted. The averaging period is entered in the range 1…1440 minutes. Read more about the averaging period of
min./max of P and Q in paragraph 7.5.
14. Heat/cooling shift (
θ
hc
)
The limit (
θ
hc
) for heat/cooling shift can be adjusted in the SETUP loop, however only in calculators ordered as meter
type 6 (heat/cooling meter). The value can be selected in the range 2…180.00
°
C as well as at 250.00
°
C if the user
wants to disable the function. The function is enabled again by setting the limit at a value in the valid area of 2…180
°
C. Heat/cooling shift is permanently disabled in other meter types and therefore, “OFF” is displayed in all other
meter types than 6. Read more about heat/cooling shift in paragraph 7.4.
Meter type: 1, 2, 3, 4, 5, 7
Meter type: 6
The frames around “OFF” will be shown
as long as the primary key remains
activated.
The first digit flashes and each digit can
now be set to a value within the range
0…9.
If you choose a value outside the valid
range (2…180.00
°
C), the value is
automatically adjusted to 250.00
°
C,
which indicates that the function has
been switched off.