MULTICAL® 803
98
Kamstrup A/S · Technical description · 5512-2360_A1_
GB
_02.2019
Application no. 5
Open system with tapping from outlet pipe
Heat energy: E1 = V1 (t1-t2)k
t1
Tap water energy: E5 = V2 (t2-t3)k
t2
t3 is measured or programmed
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t2)
Config. A = 3 (inlet)
Application no. 6
Open system with separate flow meter for tapping
Heat energy: E1 = V1 (t1-t2)k
t2
Tap water energy: E6 = V2 (t3-t4)k
t3
t3 and t4 are measured or programmed
Mass: M1 = V1 (Kmass t1)
Mass: M3 = V2 (Kmass t3)
Config. A = 4 (outlet)