MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
101
Application no. 11
2-step boiler system with 1 flow sensor
Boiler energy “B”: E3 = V1 (t2-t1)k
t1
(Upper boiler)
Boiler energy “A”: E4 = V1 (t1-t3)k
t1
(Lower boiler)
Config. A = 3 (inlet)
Application no. 30
❷
❺
Closed thermal system with 2 consumers and 1
common flow sensor
Heat energy:
E1 = V1 (t1-t2)k
t1 or t2
E13 = V1 (t3-t4)k
t1 or t2
Cooling energy:
E3 = V1 (t2-t1)k
t1 or t2
E15 = V1 (t4-t3)k
t1 or t2
Mass: M1 = V1 (Kmass t1) or
Mass: M1 = V1 (Kmass t2) depending on the
programming of inlet/outlet.
Config A = 3 (inlet) or 4 (outlet)