10.2.5
0/4…20 mA outputs (67-00-23) (PCB 5550-1005)
The module is furnished with two active analogue outputs, which can both be configured for 0…20 mA or for 4…20
mA. In addition, the outputs can be configured to any measuring value (power, flow, or temperature) and to any
range scaling. All values of the two analog outputs are updated every 10 seconds.
The total response time however
may be up to 30-40 seconds including the response time for the flow sensor, the calculator and the digital to analog
conversion. This response time has to be considered when using the analog outputs for other purposes than remote
displaying. The module must be mounted in MULTICAL
®
602. It cannot be used separately together with flow
meters.
The configuration is carried out via the menu "Base module" in METERTOOL.
The module must be powered by 24 VAC.
10.2.6
Lo pulse inputs (67-00-24) (PCB 5550-1128)
The LON-module is used for data transfer from MULTICAL
®
602 either for data reading or for regulation purposes via
the LON-bus, which is ideal for climate control and building automation among other things. The high-speed data
communication makes it possible to connect many applications to a LON-network.
The cabling between the LON-module and and the other LON-nodes consists of standard twisted pair cable of up
to 2700 m length at bus topology or 500 m length at free topology.
The module requires that MULTICAL
®
602 is externally supplied (24-VAC /230-VAC), battery supply of MULTICAL
®
602 is not possible. See paragraph 7.3 as to the function of pulse inputs VA and VB.
Regarding network variable list (SNVT) and further information on the LonWorks module we refer to data sheet
5810-1144. GB-version 5810-1043 and DE-version 5810-1044. As to installation we refer to Installation
instructions 5512-1101 (DK) or 5512-1105 (GB).
As the module is de-energised when the calculator top is not mounted, it is not possible to send Neuron ID by
activating the button on the module.
Neuron ID is sent by simultaneous activation of both front plate keys of MULTICAL
®
602. When ”Call” is displayed
the Neuron ID has been sent.