Technical Data
2.1
Approved meter data
Standard
EN 1434:2007, prEN 1434:2009 and OIML R75:2002
EU directives
Measuring Instrument Directive, Low Voltage Directive,
Electromagnetic
Compatibity
Directive
Heat meter approval
DK-0200-MI004-020
The stated minimum temperatures
apply to the type approval only.
The meter has no cut-off for low
temperature and thus measures as low
temperatures as
0.01
C and 0.01 K.
Temperature range
: 2
C…180
C
Differential range
: 3 K…170 K
Cooling meter
Temperature range
: 2
C…50
C
Differential range
: 3 K…40 K
Accuracy
E
C
(0.5 +
min
/
) %
Temperature sensors
-Type 602-A
Pt100 – EN 60 751, 2-wire connection
-Type 602-B and 602-D Pt500 – EN 60 751, 4-wire connection
-Type 602-C
Pt500 – EN 60 751, 2-wire connection
Compatible flow sensor types
-ULTRAFLOW
-Electronic meters with an active 24 V pulse output
-Mechanical meters with an electronic pick-up unit
-Mechanical meters with a Reed switch
Flow sensor sizes
kWh
qp 0.6 m
3
/h…15 m
3
/h
MWh
qp 0.6 m
3
/h…1500 m
3
/h
GJ
qp 0.6 m
3
/h…3000 m
3
/h
EN 1434 designation
Environmental class A and C
MID designation
Mechanical environment: Class M1
Electromagnetic environment: Class E1 and E2
5…55 °C, non condensing, closed location (indoor installation)