MULTICAL®
602
Kamstrup
A/S
∙
Technical
Description
∙
5512
‐
931_N1_GB_11.2016
15
3.3.1
CCC-table for MULTICAL
602
The CCC tables are divided into fast pulse codes (CCC=4XX, 2XX and 1XX) for electronic meters, e.g. ULTRAFLOW
®
,
and slow codes for e.g. reed contacts (CCC=0XX, 9XX).
CCC= 4XX
Electronic meters with fast and bounce-free pulses as well as info codes for ULTRAFLOW
®
X4
Max. pulse frequency: 128 Hz
Max. integration frequency: 1 Hz
CCC= 1XX, 2XX
Electronic meters with fast and bounce-free pulses
Max. pulse frequency: 128 Hz
Max. integration frequency: 1 Hz
CCC= 0XX
Mechanical meters delivering slow pulses with bounce (flow sensor type "L")
Max. pulse frequency: 1 Hz
Max. integration frequency: 1 Hz
CCC=9XX
Electronic
meters
with
slow and bounce free pulses
Max. pulse frequency: 1 Hz (CCC=91X), or 4 Hz (CCC=92X)
Max. integration frequency: 1 Hz
Max. integration frequency is 1 Hz for all types. The CCC codes are arranged in a way that qs+20 % (or Qmax+
20 %) does not exceed the 1 Hz in the integration frequency.
Example: CCC=107 (applies for a qp 1.5 m
3
/h meter) : 1 Hz in the integration frequency is obtained at
q = 3.6 m
3
/h.
EN 1434 makes demands on the resolution and registre size of the energy reading. MULTICAL
®
602 meets these
demands when connected to below flow sensor sizes:
kWh
qp 0.6 m
3
/h…15 m
3
/h
MWh
qp 0.6 m
3
/h…1500 m
3
/h
GJ
qp 0.6 m
3
/h…3000 m
3
/h
3.3.2
CCC codes for mechanical flow sensors with Reed switch
Number of decimals on the display
CCC
no.
Pre-
counter
Flow factor
kWh
MWh
Gcal
GJ
m³
ton
m³/h
l/h
kW
MW
l/pulses
Pulses/l
Qmax
m³/h
Flow
sensor
010 1 921600
1
-
3
3 - 0
1
- 1 1
3,0
L
011
1
921600
-
3
2
2
2
-
0
-
10
0.1
1…30
L
012
1
921600
-
2
1
1
1
-
-
2
100
0.01
10…300
L
013
1
921600
-
1
0
0
0
-
-
1
1000
0.001
100…3000
L
020
4
230400
0
3
2
2
2
-
0
-
2.5
0.4
6
L
021
4
230400
-
2
1
1
1
-
-
2
25
0.04
3…60
L
022
4
230400
-
1
0
0
0
-
-
1
250
0.004
30…600
L
Current flow (l/h or m³/h) reading is calculated on the basis of the measured period between 2 volume pulses
(see paragraph 6.5)
When one of above CCC codes has been selected both CCC (V1) and CCC (V2) must be selected from this table.
Note
: Continuous maximum water flow and permanent
>
75 K may cause overflow in the daily data logger at
CCC=010-011-012-013-150-202-205. With these combinations we recommend you to use Prog. data logger type
67-0B or type 67-00-22.