Data loggers
MULTICAL
602 contains a permanent memory (EEPROM), where the results of a number of various data loggers
are stored. The meter contains the following data loggers:
Data logging interval
Data logging depth
Logged value
Logger read-out
Yearly logger
15 years
Counter registers
LogView/MT Pro
Monthly logger
36 months
Counter registers
LogView/MT Pro
Daily logger
460 days
Consumption (increase)/day LogView/MT Pro
Hourly logger
1392 hours
Consumption (increase)/hour LogView/MT Pro
Programmable data logger
top module 67-0B and base
module 67-00-22
1080
loggings
Logging interval 1-1440 min.
(e.g. 45
days'
hour loggings
or
11 days' 15 min. loggings)
30 registers and values
AMR *),
LogView/MT Pro
Info logger
50 events (36 events can be
displayed)
Info code, date, time and
energy (E1/E3) **)
LogView/MT Pro
*) Example of AMR (Automatic Meter Reading) for the data logger is GSM/GPRS. See chapter 13.4 about LogView.
**)
Only info code and date appear from the display.
The loggers are static and therefore the register types cannot be changed, furthermore, the logging intervals are
fixed. When the last record has been written in the EEPROM the oldest one is overwritten.
6.13.1
Yearly, monthly, daily and hourly loggers
Following registers are logged every year and every month on target date as counter values. In addition, the
increases of the day and the hour are logged at midnight.
Register type
Description
Yearly
logger
Monthly
logger
Daily
logger
Hourly
logger
67-0B
67-00-22
Prog.
logger
Date (YY.MM.DD)
Year, month and day for logging times
Clock (hh.mm.ss.)
Time
- -
- -
Log Info
Status, quality stamping of log record
- -
- -
E1
E1=V1(T1-T2)k Heat energy
E2
E2=V2(T1-T2)k Heat energy
E3
E3=V1(T2-T1)k Cooling energy
E4
E4=V1(T1-T3)k Inlet energy
E5
E5=V2(T2-T3)k Returned energy or tap from outlet
E6
E6=V2(T3-T4)k Tap water energy, separate
E7
E7=V2(T1-T3)k Tap water energy from inlet
E8 E8=m
3
x T1 (inlet)
-
E9 E9=m
3
x T2 (outlet)
-
TA2
Tariff register 2
-
-
-
TA3
Tariff register 3
-
-
-
V1
Volume register for Volume 1
V2
Volume register for Volume 2
VA
Extra water or electricity meter connected to Input A
VB
Extra water or electricity meter connected to Input B
M1
Mass corrected V1
- -
M2
Mass corrected V2
- -
INFO Information
code
DATE FOR MAX. FLOW V1
Date stamp for max. flow in the period
-
-
-
MAX. FLOW V1
Value for max. flow in the period
-
-
-
DATE FOR MIN. FLOW V1
Date stamp for min. flow in the period
-
-
-
MIN. FLOW V1
Value for min. flow in the period
-
-
-
DATE FOR MAX. POWER V1
Date stamp for max. power in the period
-
-
-