Exit setup-menu
When the display value has been changed as required, hold the main key for 10 seconds, until the ”OK” segment
is displayed. The display reverts to legal reading.
The new value is checked. If it is valid, the new value is saved. If it is invalid, the old value is kept and the “OK”
segment will not be displayed within approx. 3 seconds. The display reverts to legal reading.
If you wish to exit the setup-menu without saving the new value:
1)
Remove the calculator from the base
2)
Wait until the display goes blank (up to 2.5 minutes). Meanwhile do not touch the front keys
3)
Replace the calculator on the base without pressing the front keys
Allow some seconds for the meter to boot-up without pressing the front keys. The normal display register is now
shown and the setup menu is deactivated.
Note that if the front keys are not activated for 4 minutes in the setup-menu, the setup-menu will be deactivated
and the meter will automatically return to normal operation.
No data will be stored in the meter’s memory, unless the “OK” segment is displayed.
6.17.4
Display registers supported by the setup-menu
The following registers are supported by the setup-menu:
●
Date
●
Clock
●
Primary M-Bus address (for both top and base module if mounted)
●
Preset of Input A
●
Preset of Input B
●
Meter No. for Input A
●
Meter No. for input B
●
Pulse value for Input A
●
Pulse value for Input B