MULTICAL®
602
Kamstrup
A/S
∙
Technical
Description
∙
5512
‐
931_N1_GB_11.2016
33
602-C
Application No. 3
2 string system with 2 flow sensors
Heat energy: E1 = V1(T1-T2)k
T1:Inlet or T2:Outlet
Tap water energy: E6 = V2 (T3-T4)k
T3:Inlet
T3 is measured or programmed
T4 is programmed
Flow sensor V1 is placed in inlet or outlet pipe as
chosen under PROG options.
Mass: M1 = V1 (Kmass t1) or
Mass: M1 = V1 (Kmass t2) depending on the
Inlet/Outlet programming
Mass: M2 = V2 (Kmass t3)*
602-C
Application No. 4
2 heat circuits with joint flow
Heat energy #1: E1 = V1(T1-T2)k
T2:Outlet
Heat energy #2: E7 = V2(T1-T3)k
T3:Outlet
T3 is measured or programmed
Mass: M1 = V1 (Kmass t2)
Mass: M2 = V2 (Kmass t3)*
602-C
Application No. 5
Open system with tap from outlet pipe
Heat energy: E1 = V1(T1-T2)k
T1:Inlet
Tap water energy: E5 = V2 (T2-T3)k
T2:Inlet
T3 is measured or programmed.
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t2)