183
13 Technical data
13.2
Sensor JUMO flowTRANS MAG S01/02
13.2.1
Temperatures
The temperature range of the device depends on a series of factors. These factors include the measure-
ment medium temperature, the ambient temperature, the operating pressure, the lining material, and the
approvals for the Ex-protection.
13.2.2
Storage temperature
-40 to +70 °C (-40 to +158 °F)
13.2.3
Minimum admissible pressure depending on the medium temperature
Sensor housing made of aluminum (double shell housing)
Sensor housings made of steel
13.2.4
Maximum admissible cleaning temperature
If the ambient temperature is > 25 °C, the difference must be subtracted from the max. cleaning tem-
perature. T
max
- ∆ °C. (∆ °C = T
Amb
- 25 °C)
Lining
Nominal width
p
Operation
abs
for T
Operation
a
a
Higher temperatures are allowed for CIP/SIP cleaning for a limited time (
See table 13.2.4).
Hard rubber
DN 15 to 2000 (1/2 to 80″)
0 mbar
< 90 °C (194 °F)
Soft rubber
DN 50 to 2000 (2 to 80″)
0 mbar
< 60 °C (140 °F)
PTFE
DN 10 to 600 (3/8 to 24″)
270 mbar
< 20 °C (68 °F)
400 mbar
< 100 °C (212 °F)
500 mbar
< 130 °C (266 °F)
Thick PTFE
DN 25 to 80 (1 to 3″)
0 mbar
< 180 °C (356 °F)
DN 100 to 80 (4 to 10″)
67 mbar
< 180 °C (356 °F)
DN 300 (12″)
27 mbar
< 180 °C (356 °F)
PFA
DN 3 to 200 (1/10 to 8″)
0 mbar
< 180 °C (356 °F)
ETFE
DN 25 to 600 (1 to 24″)
100 mbar
< 130 °C (266 °F)
Ceramic carbide
DN 25 to 1,000 (1 to 40″)
0 mbar
< 80 °C (176 °F)
Lining
Nominal width
p
Operation
abs
for T
Operation
a
a
Higher temperatures are allowed for CIP/SIP cleaning for a limited time (
See table 13.2.4).
Hard rubber
DN 40 to 600 (1 1/2 to 24″)
600 mbar
< 80 °C (176 °F)
PTFE
DN 25 to 600 (1 to 24″)
270 mbar
< 20 °C (68 °F)
400 mbar
< 100 °C (212 °F)
500 mbar
< 130 °C (266 °F)
CIP cleaning
Lining
T
max
T
max
minutes
T
amb
Sensor
Steam cleaning
PTFE, PFA
150 °C (302 °F)
60
25 °C (77 °F)
Liquids
PTFE, PFA
140 °C (284 °F)
60
25 °C (77 °F)
Summary of Contents for flowTRANS MAG H01
Page 2: ......
Page 22: ...1 Safety 22...
Page 68: ...5 Electrical connection 68...
Page 72: ...6 Digital communication 72...
Page 94: ...7 Startup 94...
Page 108: ...8 Parameterization 108...
Page 109: ...109 8 Parameterization...
Page 110: ...8 Parameterization 110...
Page 111: ...111 8 Parameterization...
Page 112: ...8 Parameterization 112...
Page 152: ...8 Parameterization 152...
Page 160: ...9 Advanced diagnostics functions 160...
Page 258: ...14 Annex 258...
Page 259: ......