8 Parameterization
The parameters for the filling function must be configured:
To display the data relevant to filling in the process display, one of the operator pages should be config-
ured accordingly in the "
Display
" menu:
IMPORTANT (NOTE)!
To achieve a fast response time of the filling function, damping must be switched off. The filling time
should be > 3 seconds.
Menu/parameter
Value range
Description
Totalizer/
...Batching
a
Damping
OFF
Switch damping on/off
Default setting: ON
Preset Batch Tot.
-
Sets the filling quantity.
The configured digital output is activated when the
defined filling quantity is reached.
Lag Corr. Mode
Automatic/Manual
Selects the after-flow quantity correction.
It takes a certain time to close the filling valve; this in
turn leads to an after-flow of the fluid although the fill-
ing quantity has been reached and the valve closer
contact is actuated.
"Automatic after-flow correction" corrects the defined
filling quantity by the after-flow quantity.
Lag Corr. Quantity
-100,000 to +100,000
Manual input of the after-flow quantity
Batch Tot.
Display only
After starting filling, the quantity already filled is dis-
played here.
The Totalizer restarts at zero each time filling starts
and only counts up to the defined filling quantity.
Total Batch Counter
Display only
Total number of all fills
Reset Batch Counter.
Reset filling totalizer to zero
Start/Stop Batching
Manual start/stop of filling action.
Alternatively, the digital input can be used to start/
stop the filling action.
a
Only available for JUMO flowTRANS MAG S02/H02
Menu/parameter
Value range
Description
Display/...Operator pages/
Operator page 1 (n)
Display Mode
3 lines with 9 characters
Configuration of the respective operator page
1st Line
Flowrate [unit]
Selection of the measured value displayed in the re-
spective line. You can choose between the variants
displayed in the value range.
2nd Line
Number of fills
3rd Line
Batch totalizer
Summary of Contents for flowTRANS MAG H01
Page 2: ......
Page 22: ...1 Safety 22...
Page 68: ...5 Electrical connection 68...
Page 72: ...6 Digital communication 72...
Page 94: ...7 Startup 94...
Page 108: ...8 Parameterization 108...
Page 109: ...109 8 Parameterization...
Page 110: ...8 Parameterization 110...
Page 111: ...111 8 Parameterization...
Page 112: ...8 Parameterization 112...
Page 152: ...8 Parameterization 152...
Page 160: ...9 Advanced diagnostics functions 160...
Page 258: ...14 Annex 258...
Page 259: ......