13 Technical data
13
Technical data
13.1
General information
13.1.1
Reference conditions according to EN 29104
13.1.2
Maximum measurement deviation
JUMO flowTRANS MAG S01
JUMO flowTRANS MAG S02
JUMO flowTRANS MAG H01
JUMO flowTRANS MAG H02
Measuring medium temperature
20 °C (68 °F) ±2 K
Ambient temperature
20 °C (68 °F) ±2 K
Voltage supply
Nominal voltage according to the nameplate
V
n
±1 %, frequency f ±1 %
Installation conditions
Supply side > 10 x DN pipe section
Return side > 5 x DN pipe section
Warm-up phase
30 min
IMPORTANT (NOTE)!
Q
max
DN
See table chapter 7.6 "Nominal width, measuring range", page 92.
Calibration (pulse output)
Nominal width
±0.4% of the measured value, ±0.02% QmaxDN
(standard)
DN 3 to 2,000
±0.2% of measured value, ±0.02% QmaxDN (option-
al)
DN 10 to 600, 800
Calibration (pulse output)
Nominal width
±0.3% of the measured value, ±0.02% QmaxDN
(standard)
DN 3 to 600, 800
±0.4% of the measured value, ±0.02% QmaxDN
(standard)
DN 700, 900 to 2,000
±0.2% of measured value, ±0.02% QmaxDN (option-
al)
DN 10 to 600, 800
Calibration (pulse output)
Nominal width
±0.4% of the measured value, ±0.02% QmaxDN
(standard)
DN 3 to 100
±0.2% of measured value, ±0.02% QmaxDN (option-
al)
DN 10 to 100
Calibration (pulse output)
Nominal width
±0.3% of the measured value, ±0.02% QmaxDN
(standard)
DN 3 to 100
±0.7% of the measured value, ±0.02% QmaxDN
(standard)
DN 1 to 2
Summary of Contents for flowTRANS MAG H01
Page 2: ......
Page 22: ...1 Safety 22...
Page 68: ...5 Electrical connection 68...
Page 72: ...6 Digital communication 72...
Page 94: ...7 Startup 94...
Page 108: ...8 Parameterization 108...
Page 109: ...109 8 Parameterization...
Page 110: ...8 Parameterization 110...
Page 111: ...111 8 Parameterization...
Page 112: ...8 Parameterization 112...
Page 152: ...8 Parameterization 152...
Page 160: ...9 Advanced diagnostics functions 160...
Page 258: ...14 Annex 258...
Page 259: ......