167
10 Error messages
10.2.4
Maintenance
10.3
Overview of the error statuses and alarms
Error no./
area
Text in the LCD display
Cause
Remedy
M099.027
Electronics
NV Corrupt
NV Memory, SensorMemory,
FRAM defective
Contact manufacturer
M094.034
Electronics
Current out fault
20 mA loop open, cable break or
no power is connected during op-
eration as passive 20 mA output,
max. permissible load exceeded
or hardware defective
Check for incorrect wiring or wire
break. Check that the jumper to
the 20 mA active / passive swi-
tchover is connected correctly to
the backplane in the transmitter
housing.
Comms. to MSP
Check wiring
Check whether the external power
is connected during operation as
20 mA passive.
20 mA passive?
Check BR901!
M090.014
Sensor
Errors Sensors Comms
EMC environment or loose con-
tact on the D1 or D2 terminals or
incorrect wiring or short-circuit or
moisture in the terminal box
Check for incorrect wiring (termi-
nals D1, D2), check terminal box
Bad EMC environment
Check wiring
M080.012
Operation
Display value is < 1600 h at
Q
max
Display value < 1600 h for Q
max
Change the totalizer unit
Change eng. Unit for Total-
izer
Error no./
area
Text in the
LCD display
Current
output
behavior
Digital
output
behavior
Pulse
output
behavior
Display
Error
can be
masked?
F254.038
Electronics
RAM error in Transmitter
lout at alarm
General Alarm 0 Hz
0 %
No
Contact service
F253.037
Electronics
ROM error in Transmitter
llout at alarm
General Alarm 0 Hz
0 %
No
Contact service
F252.017
Sensor
No Sensor Memory
lout at alarm
General Alarm 0 Hz
0 %
No
Check wiring
Check switch SW3?
F251.040
Electronics
FRAM error in the transmit-
ter
lout at alarm
General Alarm 0 Hz
0 %
No
Contact service
F250.016
Electronics
Tx memory fault detected
lout at alarm
General Alarm 0 Hz
0 %
No
Contact service
F248.036
Sensor
Incompatible snsTx+
lout at alarm
General Alarm 0 Hz
0 %
No
sns are not the same series
F246.032
Electronics
Defect digital potentiometer
Transmitter Hardware fault-
Contact service
lout at alarm
General Alarm 0 Hz
0 %
No
F245.047
Electronics
Stack NV Corrupt
Contact service
lout at alarm
General Alarm 0 Hz
0 %
No
Summary of Contents for flowTRANS MAG H01
Page 2: ......
Page 22: ...1 Safety 22...
Page 68: ...5 Electrical connection 68...
Page 72: ...6 Digital communication 72...
Page 94: ...7 Startup 94...
Page 108: ...8 Parameterization 108...
Page 109: ...109 8 Parameterization...
Page 110: ...8 Parameterization 110...
Page 111: ...111 8 Parameterization...
Page 112: ...8 Parameterization 112...
Page 152: ...8 Parameterization 152...
Page 160: ...9 Advanced diagnostics functions 160...
Page 258: ...14 Annex 258...
Page 259: ......