JOHNSON CONTROLS
30
FORM 160.54-O1
optiView Control Center
remote input type
(0-10V or 4-20mA; default 0-10v)When operating in
ANALOG Control Source, the LTC I/O Board accepts
a Remote Hot Water Setpoint offset in the form of either
a 0-10Vdc or 4-20mA input to the LTC I/O Board input
(TB9-3/4). This setpoint configures the LTC I/O Board
input to accept the input signal type applied. Only ap-
pears when the Hot Water Control is set enabled and the
CONTROL SOURCE setpoint (Operations Screen) is
set to ANALOG.
Control Valve output settings - type
(0-10v or 4-20mA; default 0-10v) Sets the output signal
to the Control Valve to be in the form of either 0-10Vdc
or 4-20mA. Only appears when Hot Water Control is
enabled or Head Pressure Control is enabled.
Control Valve output settings - pid output
(Direct or Reverse) Allows the output signal to the
Control Valve to be set to DIRECT or REVERSE act-
ing. When set to DIRECT, the voltage or current signal
to the Control Valve is at minimum for a 0% command
and at maximum for a 100% command. When set to
REVERSE, the voltage or current signal to the Control
Valve is at maximum for a 0% command and at mini-
mum for a 100% command. Only appears when Hot
Water Control is enabled or Head Pressure Control is
enabled.
Control Valve output settings - set
(0.0% to 100%; default 0.0%) Allows the Control Valve
to be manually set to a pre-determined position between
0.0% and 100%. Only appears when Hot Water Control
is enabled or Head Pressure Control is enabled.
Control Valve output settings - auto
Places the Control Valve in automatic control. Only
appears when Hot Water Control is enabled or Head
Pressure Control is enabled.
Change setpoints
Use to enter the Hot water Control and Head Pressure
Control PID variables below. Pressing this key places a
green box around the first changeable setpoint. Use the
up/dn, left/right arrows to place the selection box aroud
thwe desired setpoint. Wityht the setpoint selected, press
the ENTER (checkmark) key. A dialog box appears with
the range of settings. Using the numeric keys, enter de-
sired value. Then, press the ENTER (checkmark) key.
hot Water Control - p
Sets the Proportional Gain of the Hot water Control
(0.00 to 5.00; default 2.00). Use the Change Setpoints
key as described above to select/enter this setpoint. Only
appears when Hot Water Control is enabled.
hot Water Control - i
Sets the Integral Gain of the Hot Water Control (0.00
to 5.00; default 2.00). Use the Change Setpoints key as
described above to select/enter this setpoint. Only ap-
pears when Hot Water Control is enabled.
hot Water Control - d
Sets the Derivative Gain of the Hot Water Control (0.00
to 5.00; default 0.00). Use the Change Setpoints key as
described above to select/enter this setpoint. Only ap-
pears when Hot Water Control is enabled.
head pressure Control - p
Sets the Proportional Gain of the Head Pressure Control
(0.00 to 5.00; default 2.00). Use the Change Setpoints
key as described above to select/enter this setpoint. Only
appears when Head Pressure Control is enabled.
head pressure Control – i
Sets the Integral Gain of the Head Pressure Control (0.00
to 5.00; default 2.00). Use the Change Setpoints key as
described above to select/enter this setpoint. Only ap-
pears when Head Pressure Control is enabled.
head pressure Control – d
Sets the Derivative Gain of the Head Pressure Control
(0.00 to 5.00; default 0.00). Use the Change Setpoints
key as described above to select/enter this setpoint. Only
appears when Head Pressure Control is enabled.
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...