FORM 160.54-O1
137
JOHNSON CONTROLS
Select
Access Level Required:
OPERATOR
This key is used to enter the slot numbers and the min-
imum and maximum Y-Axis values of each parameter
to be trended. Pressing this key places a yellow box
around Data Point 1 Slot Number. Use the ▲ and ▼
navigation keys to place the box around the value of
Data Points 1 through 6 to be changed. With the desired
value selected, press the
key. A dialog box is displayed
permitting data entry.
Data Point Slot # (1-6)
Access Level Required:
OPERATOR
Use the SELECT key as described above and enter the
slot number from the Common Slots Screen or Master
Slot Number List of the desired parameter to be trended.
The selected parameter description will be displayed
for the Data Point. Setting this slot number to zero will
disable trending for that particular Data Point. Any or
all points can be disabled.
Data Point Min (1-6)
Access Level Required:
OPERATOR
Only displayed if the Associated Slot Number is not Zero.
This is the minimum value displayed for the Y-Axis. Se-
lecting a parameter for a Data Point sets this to the default
value, which is the lowest value allowed for that parameter.
It can be changed to a value that provides a more appro-
priate resolution for the parameter being monitored. To
change, use the SELECT key as described above and enter
the desired value. The value must always be set to a value
less than the Data Point Max. Otherwise, a red graph is
displayed on the Trend Screen with the words “
TREnD
MAX MUST BE > TREnD MIn
”. If the parameter
selected for this data point is a digital type (on/off), this
value must be set to zero (0). Zero indicates the OFF
state.
Data Point Max (1-6)
Access Level Required:
OPERATOR
Only displayed if the associated slot number is not zero.
This is the maximum value displayed for the Y-Axis. Se-
lecting a parameter for a Data Point sets this to the default
value, which is the highest value allowed for that parameter.
It can be changed to a value that provides a more appro-
priate resolution for the parameter being monitored. To
change, use the
SELECT
key as described above and enter
the desired value. The value must always be set to a value
greater than the Data Point Min. Otherwise, a red graph is
displayed on the Trend Screen with the words “TREND
MAX MUST BE > TREND MIN”. There are 20 Y-Axis
divisions. If a MIN-MAX span is selected that is not evenly
divided by 20, the Program will automatically select the
next higher MAX value that makes the span evenly divided
by 20 (If compressor application is other than “P”, ap-
plies only to Flash memory card version C.MLM.01.02
or later). For example, if 0.0 is selected as the MIN and
69.0 is selected as the MAX, the Program will insert 70.0
as the MAX value. If the parameter selected for this data
point is a digital type (on/off), this value must be set to one
(1). One indicates the on state.
NaVigatioN
Home
Causes a return to the Home Screen.
Trending
Causes a return to the Trending Screen.
Slot numbers
(Flash memory card version C.MLM.01.02 or later)
Causes a jump to a sub-screen that lists the slot numbers
of the most commonly monitored parameters. The desired
parameters to be plotted are selected from this screen.
Triggers
(Flash Memory Card version C.MLM.01.05.xxx and
later)
Causes a jump to the Advanced Trend Setup Screen,
where the start/stop Triggers can be setup. Only dis-
played if TRIGGERED has been selected as Chart
Type.
2
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...