JOHNSON CONTROLS
106
FORM 160.54-O1
setUp sCreeN
oVerVieW
This screen is the top level of the general configuration
parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, follow
-
ing instructions in YORK Service Manual 160.54-M1,
establishes this configuration per the desired operation.
This screen also serves as a gateway to more sub-screens
for defining general system parameters.
dispLaY oNLY
031-01730-000 Microboard
Chilled Liquid Pump Operation:
Displays
Standard
or
Enhanced
Motor Type:
Displays
Fixed Speed
or
Variable Speed
Refrigerant Selection:
Displays
R-22
or
R134a
Anti-Recycle:
Displays
Disabled
or
Enabled
Power Failure Restart:
Displays
Manual
or
Automatic
Liquid Type:
Displays
Water
or
Brine
Coastdown:
Displays
Standard
(150 seconds) or
Enhanced
(15
minutes – Steam Turbine applications)
Pre-Run:
Displays
Standard
(50 seconds) or
Extended
(180
seconds)
Oil Pump Package:
Displays
Fixed
Speed
or
Variable
Speed
Power Line Frequency (VSD only):
Displays
60 Hz
or
50 Hz
031-02430-000 & 031-02430-001 Microboard
Refrigerant Selection
Displays R22 or R134a
Liquid Type
Displays Water or Brine
LD14340
fig. 27
optiView Control Center
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...