JOHNSON CONTROLS
16
FORM 160.54-O1
aNaLog iNpUt raNges
The following table indicates the valid display range for each of the analog input values. In the event that the input
sensor is reading a value outside of these ranges, the < or > symbols will be displayed beside the minimum or maxi-
mum value, respectively.
*Saturation temperatures are calculated values. They will display XXX if the pressure used for the calculation is out of range.
**Not applicable to chillers equipped with Flash Memory Card version C.MLM.01.03 and later.
***7.5 PSIG Flash Memory Card Version C.MLM.01.04 and later.
aNaLog iNpUt
eNgLish raNge
MetriC raNge
LoW
high
UNits
LoW
high
UNits
Leaving Chilled Liquid temperature
0.0
82.0
°F
-17.7
27.7
°C
return Chilled Liquid temperature
0.0
94.1
°F
-17.7
34.5
°C
Leaving Condenser Liquid temperature
8.0
133.5
°F
-13.3
56.3
°C
return Condenser Liquid temperature
8.0
133.5
°F
-13.3
56.3
°C
evaporator refrigerant temperature (optional)
0.0
126.1
°F
-17.7
52.3
°C
discharge temperature
31.8
226.3
°F
-0.1
107.9
°C
oil temperature
31.8
226.3
°F
-0.1
107.9
°C
Condenser pressure (r22 and r134a)
***0.0
315.0
PSIG
0.0
2172.4
kPAG
Condenser temperature (r22)*
-122.1
130.9
°F
-85.6
54.9
°C
Condenser temperature (r134a)*
-98.7
160.1
°F
-72.6
71.7
°C
evaporator pressure (r22 – water)
49.4
128.8
PSIG
340.6
888.2
kPAG
evaporator pressure (r22 – brine)
25.0
100.0
PSIG
172.4
689.6
kPAG
evaporator pressure (r134a)
5.5
77.4
PSIG
37.9
533.7
kPAG
evaporator temperature (r22 – water)*
13.0
67.0
°F
-10.5
19.4
°C
evaporator temperature (r22 – brine)*
-18.0
51.4
°F
-27.7
10.7
°C
evaporator temperature (r134a)*
-44.9
64.7
°F
-42.7
18.1
°C
oil sump pressure (r22)
23.2
271.8
PSIG
160.0
1874.4
kPAG
oil sump pressure (r134a)
0.0
315.0
PSIG
0.0
2172.4
kPAG
oil pump pressure (r22 and r134a)
0.0
315.0
PSIG
0.0
2172.4
kPAG
high speed thrust Bearing proximity position
(Style E and earlier chillers with G, H, or J
8.0
99.0
Mils
-7.1
148.8
°C
compressors and Style F and later chillers with
J or H3 compressors)
high speed thrust Bearing
19.1
300.0
°F
-7.1
148.8
°C
drain temperature**
refrigerant Level
0.0
100.0
%
0.0
100.0
%
drop Leg refrigerant temperature
0.0
121.7
°F
-17.7
49.8
°C
LaNgUages
The Screens can be displayed in various languages.
Language selection is done on the USER Screen. The
desired language is selected from those available. Not all
languages are available. English is the default language.
If a language other than English is being displayed, an
English-only speaking person should navigate to the
USER Screen using the preceding Navigation chart
and select English per the USER Screen instructions
in this book.
optiView Control Center
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...