heat reCoVerY sCreeN
(Software Version C.OPT.01.21.307)
oVerVieW
This screen displays all parameters related to the Heat
Recovery feature. It also allows for setting of the
setpoints applicable to this feature.
The Heat Recovery feature is an optional feature and if
so equipped, it must be enabled on the SETUP Screen.
Once enabled, this screen is accessible from the CON-
DENSER Screen. If the Head Pressure Control feature is
also enabled, there is no separate Head Pressure Control
Screen. Rather, the Head Pressure Control parameters
and setpoints appear on this screen. The screen above
is shown with Heat Recovery, Hot Water Control and
Head Pressure Control enabled in ANALOG Control
Source.
When Heat recovery is enabled, the condenser flow
animation will show flow when either the Condenser
Liquid Flow Switch or the Heating Condenser Liquid
Flow Switch says flow is present. When heat recovery
is disabled, the condenser flow animation is based on
the standard Condenser Flow Switch. This screen also
serves as a gateway to controlling the Refrigerant Level,
Heat Recovery and Head Pressure Control.
A complete explanation of the Heat Recovery feature is
contained in Service Manual 160.54-M1.
LD14334
fig. 7a
optiView Control Center
Note! – Requires Login access level of SERVICE.
dispLaY oNLY
return heating Condenser Liquid temperature
Displays the temperature of the liquid as it enters the
heating condenser tube bundle.
Leaving heating Condenser Liquid temperature
Displays the temperature of the liquid as it leaves the
heating condenser tube bundle.
active hot Water setpoint
Displays the Hot Water Setpoint to which the Leav-
ing Heating Condenser Liquid Temperature is being
controlled. Only appears when Hot water Control is
enabled.
return Condenser Liquid temperature
Displays the temperature of the liquid as it enters the
standard condenser tube bundle.
Leaving Condenser Liquid temperature
Displays the temperature of the liquid as it leaves the
standard condenser tube bundle.
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...