JOHNSON CONTROLS
138
FORM 160.54-O1
adVaNCed treNd setUp sCreeN
fig. 42
00474VIP
oVerVieW
(Flash Memory Card version C.MLM.01.05.xxx and
later)
The desired data collection start/stop triggers are setup
on this screen. The trend data collection can be set to
start or stop based upon the status of up to two selected
Triggers.
The Triggers can consist of digital events or analog
parameters compared to thresholds. The Triggers can
be used individually or in combination. The digital and
analog parameters are selected from the Common Slots
Screen (or Master Slot Numbers List in this book).
The parameter selected as the Primary Trigger is com-
pared to a value selected as the Primary Test, using the
Primary Operator as a comparator. If it is evaluated as
true, then the data collection is started or stopped (after
any selected Trigger delay) per the selected Trigger
Action.
A Secondary Trigger can be evaluated with the Primary
Trigger to start/stop data collection. The Primary to Sec-
ondary Operator is used to define the Trigger combi
-
nations required to be true to start/stop data collection.
The Secondary Trigger is setup and evaluated the same
as the Primary Trigger.
Entry fields are as follows:
If Primary Trigger
Is Primary Operator Primary Test
Primary to Secondary Operator
Secondary Trigger
Is Secondary Operator Secondary Test
Then Trigger Action the Data Collection
With a delay of Trigger Delay
After the desired Triggers are set, the START key on
the TREND Screen must be manually pressed before
the triggers will be evaluated. While waiting for the
triggers to start or stop data collection, a status message
is displayed in the upper right corner of the TREND
Screen describing the pending action.
dispLaY oNLY
None
prograMMaBLe
Primary Trigger
Access Level Required:
OPERATOR
Selects the first parameter to be evaluated. Selection is
made from the Slot Numbers listing on the Trend Com-
mon Slots Screen or the Master Slot Numbers List in
optiView Control Center
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...