FORM 160.54-O1
139
JOHNSON CONTROLS
2
this book. Setting this slot number to zero disables the
Primary Trigger.
Primary Operator
Access Level Required:
OPERATOR
Selects the comparator for the Primary Trigger’s rela-
tionship to the Primary Test. If the Primary Trigger is
an analog value, selections are: <, <=, =, =>, >. If the
Primary Trigger is a digital event, selections are: Equal
To, Not Equal To.
Primary Test
Access Level Required:
OPERATOR
Selects the value or condition that the Primary Trigger
is compared to. Selection ranges from the Primary Trig-
ger minimum value to the Primary Trigger maximum
value.
Trigger Action
Access Level Required:
OPERATOR
Selects whether the trend data collection will Start or
Stop when the Trigger comparisons are true. If set to
Start, data collection will stop after one screen of data
is collected.
Trigger Delay
Access Level Required:
OPERATOR
Allows the data collection start or stop to be delayed
after the Triggers evaluate as true. The delay is se-
lectable from 1 to 864000 seconds (10 days). Display
is in days, hours, minutes and seconds. The delay timer
begins when the triggers evaluate as true. If the Trigger
Action is set to Start, data collection will begin after the
triggers evaluate as true and the delay timer has elapsed.
If the Trigger Action is set to Stop, data collection will
stop after the Triggers evaluate as true and the delay
timer has elapsed.
Primary to Secondary Operator
Access Level Required:
OPERATOR
Selects whether the Primary Trigger, Secondary Trig-
ger or both have to be true in order to start or stop data
collection. Selections are AND, OR, XOR and None. If
NONE is selected, the Secondary Trigger is disabled.
Data collection will start/stop (as selected with Trigger
Action) when:
•
If AND selected: Both Primary AND Secondary are
true
•
If OR selected: Either Primary OR Secondary (or
both) are true
•
If XOR selected: Either Primary OR Secondary (but
not both) are true
Secondary Trigger
Access Level Required:
OPERATOR
Selects the second parameter to be evaluated. Selection
is made from the Slot Numbers listing on the Trend
Common Slots Screen or the Master Slot Numbers List
in this book. Setting this slot number to zero disables
the Secondary Trigger.
Secondary Operator
Access Level Required:
OPERATOR
Selects the comparator for the Secondary Trigger’s rela-
tionship to the Secondary Test. If the Secondary trigger
is an Analog value, selections are: <, <=, =, =>, >. If
the Secondary Trigger is a digital event, selections are:
Equal To, Not Equal To.
Secondary Test
Access Level Required:
OPERATOR
Selects the value or condition that the Secondary Trigger
is compared to. Selection ranges from the Secondary Trig-
ger minimum to the Secondary Trigger maximum.
NaVigatioN
Home
Causes an instant return to the Home Screen.
Trend Setup
Causes an instant return to the Trend Setup Screen.
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...