JOHNSON CONTROLS
64
FORM 160.54-O1
optiView Control Center
Variable Speed Oil Pump Speed Control:
Set
Access Level Required:
SERVICE
This key allows the user to specify a fixed manual speed
at which the VSOP will run.
Raise
Access Level Required:
SERVICE
This key puts the VSOP control into Manual Mode and
increments the present Speed Command by 0.5 Hz.
Lower
Access Level Required:
SERVICE
This key puts the VSOP control into Manual Mode and
decrements the present Speed Command by 0.5 Hz.
Auto
Access Level Required:
SERVICE
This key returns the VSOP to Automatic Mode where
control is based on the Oil Pressure setpoint.
Manual Pump
Access Level Required:
OPERATOR
This key puts the Oil Pump control in Manual Mode and
forces it to RUN. The Oil Pump is limited to running for
a maximum of ten (10) minutes. If a longer running time
is desired, this key must be pressed again. Manual Oil
Pump control is disabled (and the button hidden) during
system prelube, system run, proximity probe calibration,
seal lubrication, and system coastdown.
NaVigatioN
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...