This screen displays all information pertinent to the
Medium Voltage Solid State Starter (MVSSS). Soft-
ware version C.OPT.01.15.307 (or later) is required for
MVSSS applications.
dispLaY oNLY
Motor Run (LED)
Indicates when the Optiview Control Center is com-
manding the motor to run.
Motor Current % Full Load Amps
Displays the motor current as a percentage of Job Full
Load Amps setpoint.
Current Limit Setpoint
Displays the Current Limit in use. This value could come
from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC input
in Analog Remote mode, PWM signal in Digital Remote
mode, Microgateway interface in ISN Remote mode or
a locally programmed value in Local mode.
MediUM VoLtage soLid state starter sCreeN
fig. 18a
Pulldown Time Left
Displays the time remaining in the programmed
pulldown period.
Input Power
Displays the kilowatts measured by and transmitted
from the starter.
KW Hours
Displays the cumulative kilowatt hours. The microboard
calculates this value from the Input Power transmitted
from the starter. When the number exceeds 999999
KWH, the value will rollover to zero.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage as measured by
and transmitted from the starter.
Current – Phase A, B, C
Displays the 3-phase motor current as measured by and
transmitted from the starter.
Starter Model
Displays the starter model number as transmitted from
the starter.
optiView Control Center
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...