fig. 46–
SAMPLE PRINTOUT (SETPOINTS)
YORK SetpOintS
ChilleR id 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 1999 8:48:27 AM
Software Versions
----------------------------------------------------------------------------------
Controls
= C.MLM.01.04
BIOS
= C.MLM.00.00
Kernel
= 0.18
GUI
= 0.28
SIO
= 0.23
GPIC
= 0.04
Ext I/O
=
0110112091996
[Skip if External I/O board is not activated]
VSD [Skip if Motor Type is not VSD]
= C.VSD.00.00
SSS [Skip if Motor Type is not Mod B SSS] = C.SSS.01.01
System Information
----------------------------------------------------------------------------------
System Language
= English
Data Display Mode
= English
Control Source
= Local
Remote Analog Input Range
= 0–10 Volts
Clock
= Enabled
Jumper Settings
----------------------------------------------------------------------------------
Pre-Run
= Standard
Coastdown
= Standard
Chilled Liquid Pump Operation
= Standard
Refrigerant Selection
= R22
Anti-Recycle
= Enabled
Power Failure Restart
= Auto
Liquid Type
= Water
Motor Type
= Fixed Speed
Printer Setup
----------------------------------------------------------------------------------
Automatic Printer Logging
= Disabled
Log Start Time
= 12:00 am
Output Interval
= 60 Min
Printer Type
= Okidata
Baud
= 9600 Baud
Data Bits
= 8 Bits
Parity
= None
Stop Bits
= 1 Bit
COM 2 Setup
----------------------------------------------------------------------------------
Baud
= 19200 Baud
Data Bits
= 8 Bits
Parity
= Odd
Stop Bits
= 1 Bit
Evaporator
----------------------------------------------------------------------------------
Leaving Chilled Local Setpoint
= 45.0 ~F
Leaving Chilled ISN Setpoint
= 45.0 ~F
Leaving Chilled Modem Setpoint
= 45.0 ~F
Leaving Chilled Analog Setpoint
= 45.0 ~F
Leaving Chilled Digital Setpoint
= 45.0 ~F
Remote Range
= 10.0 ~F
Sensitivity
= Normal
Restart Offset
= 0.0 ~F
Restart Setpoint
= 45.0 ~F
Shutdown Offset
= 4.0 ~F
Shutdown Setpoint
= 41.0 ~F
Brine Low Evaporator Cutout
= 54.3 Psig
Smart Freeze
= Off
Refrigerant
= Enabled
Condenser
----------------------------------------------------------------------------------
High Pressure Warning Threshold
= 246.3 Psig
Drop Leg
= Enabled
Oil Sump
----------------------------------------------------------------------------------
Oil Pump Package
= Variable Speed
Standby Lube
= On
[Skip the following section if Variable Speed Oil Pump
is not installed]
Variable Speed Oil Pump
----------------------------------------------------------------------------------
Pressure Setpoint
= 35 Psid
Control Period
= 0.9 Sec
Proximity Probe
----------------------------------------------------------------------------------
High Speed Thrust Bearing Proximity Referenc = 41 Mils
[Skip the following section if Liquid Level is not
enabled]
Refrigerant Level Control
----------------------------------------------------------------------------------
Level Control
= On
Setpoint
= 50 %
Period
= 3.5 Sec
Proportion Limit Open
= 15 %
Proportion Limit Close
= 45 %
Rate Limit Open
= 10 %
Rate Limit Close
= 10 %
[Skip the following section if Hot Gas Bypass is not
enabled]
Hot Gas
----------------------------------------------------------------------------------
Hot Gas
= Enabled
Hold Period
= 30 Min
Close Percentage
= 5 %
Minimum Load
= 1 ~F
Maximum Open
= 80 %
Surge
----------------------------------------------------------------------------------
Surge Sensitivity
= 0.3
Shutdown
= Enabled
Extended Run
= Disabled
Count Limit
= 15
Count Window
= 5 Min
printers
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...