FORM 160.54-O1
109
JOHNSON CONTROLS
2
Standard
Extended
“Warning – High Pressure Limit” – Maximum allowable value (PSIG):
162.5
193
“Condenser – High Pressure” – Trip/reset threshold (PSIG):
180/120
200/140
“Condenser – High Pressure Stopped” – Trip/reset threshold (PSIG):
160/160
170/170
PRV Position
(Software version C.OPT.01.21.307 and later)
Access Level Required:
SERVICE
New production chillers after June 2009 can be equipped
with an optional Pre-rotation Vanes Potentiometer,
regardless of other options. This setpoint allows the
software to be used in all YK chillers, whether equipped
with the potentiometer or not. The PRV position will be
shown on respective screens when Enabled.
• Enabled – Automatically set to this setting if Hot
Gas Bypass or Variable Geometry Diffuser (VGD)
is enabled on the OPERATIONS Screen or Motor
Drive Type Setpoint is set to VSD or MVVSD. The
actual connection point of the potentiometer is deter-
mined by the equipment configuration: If equipped
with a VSD in YORK protocol configuration, it is
connected to the ACC Board; in MODBUS protocol
configuration, it is connected to the Microboard J7.
If not equipped with VSD, but equipped with Hot
Gas Bypass, the connection point is determined by
which I/O Board is present: with I/O Board 371-
02514-000, it is connected to this board; otherwise,
it is connected to the Microboard J7. If not equipped
with Hot Gas Bypass but equipped with a VGD, it
is connected to the Microboard J7.
• Disabled – Set to this position when not equipped
with a PRV potentiometer. If equipped with a VSD,
MVVSD or the Hot Gas Bypass or Variable Geom-
etry Diffuser is enabled, this setpoint is automati-
cally enabled and cannot be set to disabled.
Heat Recovery
(Software version C.OPT.01.21.307 and later)
Access Level Required:
SERVICE
Allows the Service Technician to enable or disable
the Heat Recovery feature. Refer to Service Manual
160.54-M1.
Head Pressure Control
(Software version C.OPT.01.21.307 and later)
Access Level Required:
SERVICE
Allows the Service Technician to enable or disable the
Head Pressure Control feature. Refer to Service Manual
160.54-M1.
NaVigatioN
Home
Access Level Required
: VIEW
Causes an instant return to the Home Screen.
Schedule
Access Level Required
: VIEW
Moves to the sub-screen allowing definition of the chiller
operation schedule.
Diagnostics
Access Level Required
: SERVICE
Moves to the sub-screen allowing limited diagnostic
capability while operating. Refer to YORK Service
Manual 160.54-M1
Comms
Access Level Required
: VIEW
Moves to the sub-screen allowing configuration of sys
-
tem communications.
Printer
Access Level Required
: VIEW
Moves to the sub-screen allowing configuration and
control of printer functions.
Sales Order
Access Level Required
: VIEW
Moves to the sub-screen displaying the Sales Order
information for the chiller system.
Operations
Access Level Required
: VIEW
Moves to the sub-screen displaying operating parameters
of the chiller system.
User
Access Level Required
: VIEW
Moves to the sub-screen allowing configuration of user
preferences.
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...