FORM 160.54-O1
101
JOHNSON CONTROLS
Operating Hours Since Last Motor Lubrication
Displays the run hours (in whole hours) accumulated
since the last motor lubrication. The value is reset to
zero whenever the Operating Hours (on the Operations
Screen) is reset to zero or whenever the Operator enters
his/her initials, name or user ID using the Motor Lube
Acknowledge key.
prograMMaBLe
Motor Lube Acknowledge
Access Level Required
: OPERATOR
When the motor lubrication has been performed, the
Operator must acknowledge the lubrication has been
performed. This is done by entering his/her initials,
name or user ID as a 3 to 8 character string. The entry
is displayed as the Operator Initials at Last Lubrication.
The date and time of this entry is automatically logged
as the Date of Last Motor Lubrication and Time of Last
Motor Lubrication. This entry also resets the Operating
Hours Since Last Lubrication to zero.
This entry also resets the motor lubrication warning
messages: “WARNING – MOTOR BEARING LUBE
SUGGESTED”, “WARNING – MOTOR BEARING
LUBE REQUIRED” and safety shutdown “MOTOR –
LACK OF BEARING LUBRICATION”.
Enter your initials, name or user ID using the following
procedure. The entry must be a minimum of 3 characters
and a maximum of 8 characters.
1. At the keypad, log in at OPERATOR access level
using Password 9 6 7 5. If resetting the safety shut-
down “MOTOR – LACK OF LUBRICATION”,
place COMPRESSOR switch in Stop-reset (O)
position.
2. Press the Motor Lube Acknowledge key on the Mo-
tor Lubrication Screen. A dialog box appears. A red
box highlights the first changeable location.
3. Use the ▲▼keys to scroll sequentially through the
alphabet to enter letters or numbers. Each time the
▲ is pressed, the next higher sequential alphabet
letter or number is displayed. Each time the ▼is
pressed, the next lower alphabet letter or number
is displayed. When the desired letter or number is
displayed, use the ► key to forward space the red
box for the next entry. Use the ◄ key to backspace,
if necessary. To write over an existing entry or to
place a blank space, scroll to the beginning of the
alphabet. The selection prior to the letter A is a blank
space. Use the ● key to enter a period/decimal point.
During the entry process, if it is desired to exit the
dialog box and retain the previous entry, press the
CANCEL (X) key.
4. When all of the desired characters have been entered,
press the ENTER (√) key.
Motor Lube Date
Access level required
: ADMIN
Allows modification of the Date of Last Motor Lubri
-
cation.
Auto Lube
(Software version C.OPT.01.16.XXX and later)
Access Level Required
: SERVICE
This setpoint accommodates those chillers that are
equipped with the optional Automatic Motor Lubrication
hardware that automatically lubricates the motor at regu-
lar intervals. Since chillers equipped with this hardware
don’t require manual lubrication, the lubrication warn-
ings displayed at 1000, 1200 and 1400 (safety shutdown)
operating hours since last lubrication are unnecessary.
Therefore, when the automatic lubrication hardware
is present, this setpoint must be ENABLED. With this
setting, no lubrication warnings or safety shutdown will
occur. If DISABLED, as it should be when not equipped
with the automatic lubrication hardware, the motor
lubrication warnings and safety shutdown will occur at
the associated operating hours. Service technicians refer
to procedure in Service Manual 160.54-M1.
Shutdown
(Software version C.OPT.01.16.XXX and later)
Access Level Required
: SERVICE
If the Auto Lube setpoint above is set to DISABLED,
the SHUTDOWN Setpoint is used to enable or dis-
able the safety shutdown that occurs at 1400 operating
hours since last lubrication. The safety shutdown can
be enabled or disabled per the customer’s preference.
If enabled, the safety shutdown will occur at the normal
1400 hours. If disabled, a warning will be displayed but
the safety shutdown will not occur. Service Technicians
refer to procedure in Service Manual 160.54-M1.
NaVigatioN
Home
Access Level Required
: VIEW
Causes an instant return to the Home Screen
Motor
Access Level Required
: VIEW
Causes an instant return to the Motor Screen
2
Summary of Contents for YORK YK MaxE
Page 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...