GD310-UL series VFD
Function parameter
-62-
Function
code
Name
Description
Default
value
Modify
P04.24
Vibration
control factor
at high
frequency of
motor 2
canceled by adjusting this parameter.
Setting range of P04.23: 0
–100
Setting range of P04.24: 0
–100
Setting range of P04.25: 0.00Hz
–P00.03 (max
frequency)
10
○
P04.25
Vibration
control
threshold of
motor 2
30.00Hz
○
P04.26
Energy-saving
operation
0: No operation
1: Automatic energy-saving operation
Motors will automatically adjust the output voltage to
save energy when light loads.
0
◎
P04.27 Voltage setting
Select the output setting channel at V/F curve
separation.
0: Keypad: the output voltage is determined by
P04.28.
1: AI1;
2: AI2;
3: AI3;
4: HDI;
5: Multi-step speed;
6: PID;
7: MODBUS communication;
8: PROFIBUS/CANopen communication;
9: Ethernet communication;
10: Reserved
Note
: 100% corresponds to the rated voltage of the
motor.
0
○
P04.28
Keypad setting
voltage
The function code is the voltage displaying when the
voltage is set through keypad.
The setting range: 0.0%
–100.0%
100.0%
○
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the VFD
accelerates from the output minimum voltage to the
output maximum voltage.
Voltage decreasing time is the time when the VFD
decelerates from the output maximum voltage to the
output minimum voltage.
The setting range: 0.0
–3600.0s
5.0s
○
P04.30
Voltage
decreasing
time
5.0s
○
Summary of Contents for GD310-011P-4-UL
Page 1: ......
Page 269: ...6 6 0 0 1 0 0 3 9 3 ...