GD310-UL series VFD
Function parameter
-67-
Function
code
Name
Description
Default
value
Modify
Sln
FWD
REV
Direction
ON
OFF→ON
ON
Forward
OFF
Reverse
ON
ON
OFF→
ON
Forward
OFF
Reverse
ON→OFF
Decelerate
to stop
Note
:
for the 2-wire running mode, when FWD/REV
terminal is valid, the VFD stop because of the
stopping command from other sources, even the
control terminal FWD/REV keeps valid; the VFD
won’t work when the stopping command is canceled.
Only when FWD/REV is re-launched, the VFD can
start again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop and
terminal control (see P07.04).
P05.14
Switch-on
delay of S1
terminal
The function code defines the corresponding delay
time of electrical level of the programmable terminals
from switching on to switching off.
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000
–50.000s
0.000s
○
P05.15
Switch-off
delay of S1
terminal
0.000s
○
P05.16
Switch-on
delay of S2
terminal
0.000s
○
P05.17
Switch-off
delay of S2
terminal
0.000s
○
P05.18
Switch-on
delay of S3
terminal
0.000s
○
P05.19
Switch-off
delay of S3
terminal
0.000s
○
P05.20
Switch-on
delay of S4
terminal
0.000s
○