GD310-UL series VFD
Basic operation instruction
-116-
Current running
command channel
P00.01
Multi-function
terminal 36
Switch to keypad
Multi-function
terminal 37
Switch to to terminal
Multi-function terminal 38
Switch to to
communication
Keypad running
command channel
/
Terminal running
command channel
Communication running
command channel
Terminal running
command channel
Keypad running
command channel
/
Communication running
command channel
Communication
running command
channel
Keypad running
command channel
Terminal running
command channel
/
Note
:
“/”
means the multi-function terminal is invalid on the current given channel.
Relative parameters table:
Function
code
Name
Description
Default
value
P00.00
Speed control mode
0: SVC mode 0 (apply to AM and SM)
1: SVC mode 1 (applying to AM)
2: SVM control
1
P00.01
Run command channel
0: Keypad running command
1: Terminal running command channel
(“LOCAL/REMOT” flickering)
2: Communication running command channel
(“LOCAL/REMOT” on);
0
P00.02
Communication running
commands
0: MODBUS communication channel
1:
PROFIBUS/CANopen communication
channel
2: Ethernet communication channel
3: Reserved
0
P00.18
Function
restore parameter
0: No operation
1: Restore the default value
2: Cancel the fault record
0
P00.15
Motor parameter
autotuning
0: No operation
1: Rotating autotuning
2: Static autotuning 1 (autotune totally)
3: Static autotuning 2 (autotune part of the
parameters)
0
P02.00
Motor type 1
0: Asynchronous motor
1: Synchronous motor
0
Summary of Contents for GD310-011P-4-UL
Page 1: ......
Page 269: ...6 6 0 0 1 0 0 3 9 3 ...