GD310-UL series VFD
Communication protocol
-202-
Function
instruction
Address
definition
Data meaning instruction
R/W
attribute
Operation
frequency
3000H 0
–Fmax (unit: 0.01Hz)
R
Setting frequency 3001H 0
–Fmax (unit: 0.01Hz)
R
Bus voltage
3002H 0.0
–2000.0V (unit: 0.1V)
R
Output voltage
3003H 0
–1200V (unit: 1V)
R
Output current
3004H 0.0
–3000.0A (unit: 0.1A)
R
Rotation speed
3005H 0
–65535 (unit: 1RPM)
R
Output power
3006H -300.0
–300.0% (unit: 0.1%)
R
Output torque
3007H -250.0
–250.0% (unit: 0.1%)
R
Close loop setting
3008H -100.0
–100.0% (unit: 0.1%)
R
Close loop
feedback
3009H -100.0
–100.0% (unit: 0.1%)
R
Input IO state
300AH 000
–1FF
R
Output IO state
300BH 000
–1FF
R
Analog input 1
300CH 0.00
–10.00V (unit: 0.01V)
R
Analog input 2
300DH 0.00
–10.00V (unit: 0.01V)
R
Analog input 3
300EH 0.00
–10.00V (unit: 0.01V)
R
Analog input 4
300FH /
R
Read input of
high-speed pulse 1
3010H 0.00
–50.00kHz (unit: 0.01Hz)
R
Read input of
high-speed pulse 2
3011H /
R
Read the current
stage of multi-step
speed
3012H 0
–15
R
External length
3013H 0
–65535
R
External counting
3014H 0
–65535
R
Torque setting
3015H -300.0
–300.0% (unit: 0.1%)
R
Identifying code of
the VFD
3016H /
R
Fault code
5000H /
R
R/W characteristics means the function is with read and write characteristics. For example,
“communication control command” is writing chrematistics and control the VFD with writing command
(06H). R characteristic can only read other than write and W characteristic can only write other than
read.
Note
:
when operate on the VFD with the table above, it is necessary to enable some parameters. For
example, the operation of running and stopping, it is necessary to set P00.01 to communication
Summary of Contents for GD310-011P-4-UL