GD310-UL series VFD
Basic operation instruction
-124-
5. User-defined V/F curve (V/F separation) function
V /F curve
Linear V/F curve
Multi-dots V/F curve
Self-defined V/F curve
2.0th power of torque V/F curve
1.7th power pf torque V/F curve
1.3th power of torque V/F curve
PWM output
Frequency setting
Voltage setting
P04.29 voltage ACC time
P04.30 voltage DEC time
P04.31 output Max. voltage
P04.32 output Mini voltage
P00.11 ACC 1
P00.12 DEC 1
P00.04 upper limit of the running
frequency
P00.05 lower limit of the running
frequency
P04.00 motor 1V/F curve setting
0
1
2
3
4
5
6
7
8
9
10
Keypad
AI1
PROFIBUS
MODBUS
PID
Multi-stage speed
HDI
AI3
AI2
Erthernet
CAN
P04.27(voltage setting
channel selection)
Keypad setting voltage
P04.28
0
1
2
3
4
5
6
7
8
9
10
11
Keypad
AI1
PROFIBUS
MODBUS
PID
Multi-stage speed
Simple PLC
HDI
AI3
AI2
Erthernet
CAN
P00.06
(
A frequency
command selection
)
Keypad setting frequency
P00.10
0
1
2
3
4
5
When the user selects the user-defined V/F curve function in Goodrive310-UL series VFDs, they can
set the given channel of voltage and frequency and the corresponding ACC/DEC time, or the two can
combine to form a real-time curve.
Note
: the application of V/F curve separation can be used in many cases with various kinds of power
supply of the VFD. But the users should set and adjust the parameters with caution. Incorrect
parameters may cause damage to the VFD.
Function
code
Name
Description
Default
value
P00.00
Speed control mode
0: SVC mode 0 (apply to AM and SM)
1: SVC mode 1 (applying to AM)
2: SVM control
1
P00.03
Max. output frequency
P00.04
–400.00Hz
60.00Hz
P00.04
Upper limit of the running
frequency
P00.05
–P00.03
60.00Hz
P00.05
Lower limit of the running
frequency
0.00Hz
–P00.04
0.00Hz
P00.11
ACC time 1
0.0
–3600.0s
Depend on
model
P00.12
DEC time 1
0.0
–3600.0s
Depend on
model
P02.00
Motor type 1
0: Asynchronous motor
1: Synchronous motor
0