GD310-UL series VFD
Function parameter
-108-
P15 Group PROFIBUS/CANopen function
Function
code
Name
Description
Default
value
Modify
P15.00
Module type
0: PROFIBUS
1: CANopen
Select communication protocol
0
◎
P15.01
Module
address
0
–127
This function code is used to designate the address
of the VFD.
Note
: 0 is the broadcast address, when set it as
broadcast address, only receive the radio command
of the upper monitor other than answering the upper
monitor.
2
◎
P15.02
PZD2
receiving
0: Invalid
1: Setting frequency (0
–Fmax (unit: 0.01Hz))
2: PID reference, range (0
–1000, 1000 corresponds
to 100.0%)
3: PID feedback, range (0
–1000, 1000 corresponds
to 100.0%)
4: Torque setting (-3000
–3000, 1000 corresponds to
100.0% the rated current of the motor)
5: Upper frequency of forward rotation
(0
–Fmax (unit: 0.01Hz))
6: Upper frequency of reverse rotation (0
–Fmax (unit:
0.01Hz))
7: Electromotion torque upper limit (0
–3000, 1000
corresponds to 100.0%of the rated current of the
motor)
8: Braking torque upper limit (0
–2000, 1000
corresponds to 100.0% of the rated current of the
motor)
9: Virtual input terminals command
Range: 0x000
–0x1FF
10: Virtual output terminals command
Range: 0x00
–0x0F
11: Voltage setting value (special for V/F separation)
(0
–1000, 1000 corresponds to 100.0% the rated
voltage of the motor)
12: AO output set value 1 (-1000
–1000, 1000
0
○
P15.03
PZD3
receiving
0
○
P15.04
PZD4
receiving
0
○
P15.05
PZD5
receiving
0
○
P15.06
PZD6
receiving
0
○
P15.07
PZD7
receiving
0
○
P15.08
PZD8
receiving
0
○
P15.09
PZD9
receiving
0
○
P15.10
PZD10
receiving
0
○
P15.11
PZD11
receiving
0
○
P15.12
PZD12
receiving
0
○