GD310-UL series VFD
Basic operation instruction
-115-
Start
Power on after right wiring
Restore to the factory
parameters
(
P00.18=1
)
Motor type selection
(
P02.00
)
Set P02.01~P02.05
Set P02.15~P02.19
Press QUICK/JOG to jog
If the rotation direction is wrong, power off
to change the wires and repower on
Set autotuning
Set P00.15=1
Set P00.15=3
Press RUN to autotune and
then stop
Set running frequency
Set
(
P00.00
)
P00.00=0
P00.00=1
SVPWM control mode
(
P00.00=2
)
Set P03
Set P03
Set P04
Set P01
Run
Stop
End
Set
(
P00.01,P00.02
)
Set P00.15=2
Synchronous motor
Asynchronous motor
Note
:
If fault occurs, please do as the
“Fault Tracking”. Estimate the fault reason and settle the issue.
Besides P00.01 and P00.02, terminal command setting can also be used to set the running command
channel.