GD310-UL series VFD
Basic operation instruction
-144-
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.15
P06.16
AO1
AO2
HDO
P06.17
P06.18
P06.19
P06.20
P06.22
P06.23
P06.24
P06.25
P06.27
P06.28
P06.29
P06.30
P06.26
P06.21
P06.31
(default value is 0)
(default value is 0)
default value is 0)
P06.00
(
HDO output type selection
)
0
Running frequency
1
Set frequency
3
Running rotation speed
4
Output current (relative to the inverter)
6
Output voltage
7
Output power
9
Output torque
10
Analog AI1 input value
12
Analog AI3 input value
13
HDI input value
15
MODBUS communication setting 2
16
PROFIBUS communication setting
1
2
Ramp given frequency
5
Output current ( relative to the motor)
8
Set torque
11
Analog AI2 input value
14
MODBUS communication setting 1
17
PROFIBUS communication setting 1
18
Torque current (relative to the nominal
current of the motor)
19
Exciting current ( relative to the nominal
current of the motor)
20
Reserved
0
1
P06.00
0 :
open collector high speed pulse
output
1 : open collector output
P06.01
,
P06.02
,
P06.03
,
P06. 04 output selection
Analog output curve setting
Analog output selection
Analog output filter setting
(
Output instructions:
Set value
Function
Instructions
0
Running frequency
0
–the max output frequency
1
Set frequency
0
– the max output frequency
2
Ramp given frequency
0
– the max output frequency
3
Running speed
0
–2 times of the rated synchronous rotation
speed of the motor
4
Output current (relative to the VFD)
0
–2 times of the rated current of the VFD
5
Output current (relative to the motor) 0
–2 times of the rated current of the VFD
6
Output voltage
0
–1.5 times of the rated voltage of the VFD
7
Output power
0
–2 times of the rated power
8
Setting torque value
0
–2 times of the rated current of the motor
9
Output torque
0
–2 times of the rated current of the motor
10
AI1
0
–10V/0–20mA
11
AI2
0
–10V/0–20mA
12
AI3
-10V
–10V
13
HDI
0.00
–50.00kHz
14
Setting value 1 of MODBUS
communication
-1000
–1000, 1000 corresponds to 100.0%