GD310-UL series VFD
Function parameter
-60-
Function
code
Name
Description
Default
value
Modify
P04.03
V/F frequency
1 of motor 1
Output voltage
Output
frequency
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
When P04.00 =1, the user can set V//F curve
through P04.03
–P04.08.
V/F is generally set according to the load of the
motor.
Note
: V1
<
V2
<
V3, f1
<
f2
<
f3. Too high low
frequency voltage will heat the motor excessively or
cause damage. The VFD may stall when overcurrent
or overcurrent protection.
Setting range of P04.03: 0.00Hz
–P04.05
Setting range of P04.04: 0.0%
–110.0%
Setting range of P04.05: P04.03
– P04.07
Setting range of P04.06: 0.0%
–110.0% (the rated
voltage of motor 1)
Setting range of P04.07: P04.05
– P02.02 (the rated
frequency of motor 1) or P04.05
– P02.16 (the rated
frequency of motor 1)
Setting range of P04.08: 0.0%
–110.0% (the rated
voltage of motor 1)
0.00Hz
○
P04.04
V/F voltage 1
of motor 1
00.0%
○
P04.05
V/F frequency
2 of motor 1
00.00Hz
○
P04.06
V/F voltage 2
of motor 1
00.0%
○
P04.07
V/F frequency
3 of motor 1
00.00Hz
○
P04.08
V/F voltage 3
of motor 1
0.00%
○
P04.09
V/F slip
compensation
gain of motor 1
This function code is used to compensate the
change of the rotation speed caused by load during
compensation SVPWM control to improve the rigidity
of the motor. It can be set to the rated slip frequency
of the motor which is counted as below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
function code is P02.02; n is the rated rotating speed
of the motor and its function code is P02.03; p is the
pole pair of the motor. 100.0% corresponds to the
rated slip frequency
△
f.
Setting range: 0.0
–200.0%
100.0%
○
P04.10
Vibration
control factor
In SVPWM control mode, current fluctuation may
10
○