GD310-UL series VFD
Basic operation instruction
-117-
Function
code
Name
Description
Default
value
P02.01
Rated power of
asynchronous motor 1
0.1
–3000.0kW
Depend on
model
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz
–P00.03 (the max frequency)
60.00Hz
P02.03
Rated speed of
asynchronous motor 1
1
–36000rpm
Depend on
model
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depend on
model
P02.05
Rated current of
asynchronous motor 1
0.8
–6000.0A
Depend on
model
P02.15
Rated power of
synchronous motor 1
0.1
–3000.0kW
Depend on
model
P02.16
Rated frequency of
synchronous motor 1
0.01Hz
–P00.03 (the max frequency)
60.00Hz
P02.17
Number of poles pairs
for synchronous motor 1
1
–50
2
P02.18
Rated voltage of
synchronous motor 1
0
–1200V
Depend on
model
P02.19
Rated current of
synchronous motor 1
0.8
–6000.0A
Depend on
model
P05.01
–P0
5.09
Multi-function digital
input terminals
(S1
–S8, HDI) function
selection
36: Shift the command to keypad
37: Shift the command to terminals
38: Shift the command to communication
P07.01
Parameter copy
The function code determines the manner of
parameters copy.
0: No operation
1: Upload the local function parameter to the
keypad
2: Download the keypad function parameter to
local address (including the motor parameters)
3: Download the keypad function parameter to
local address (excluding the motor parameter
of P02 and P12 group)
4: Download the keypad function parameters to
local address (only for the motor parameter of
P02 and P12 group)
0