GD310-UL series VFD
Function parameter
-72-
Function
code
Name
Description
Default
value
Modify
P06.06
Y1 switch-on
delay time
The function code defines the corresponding delay
time of the electrical level change during the
programmable terminal switching on and off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
The setting range: 0.000
–50.000s
Note
: P06.08 and P06.08 are valid only when
P06.00=1.
0.000s
○
P06.07
Y1 switch-off
delay time
0.000s
○
P06.08
HDO
switch-on
delay time
0.000s
○
P06.09
HDO
switch-off
delay time
0.000s
○
P06.10
RO1 switch-on
delay time
0.000s
○
P06.11
RO1 switch-off
delay time
0.000s
○
P06.12
RO2 switch-on
delay time
0.000s
○
P06.13
RO2 switch-off
delay time
0.000s
○
P06.14
AO1 output 0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Running rotation speed (relative to twice the motor
synchronous speed)
4: Output current (relative to twice the rated current
of the VFD)
5: Output current (relative to twice the rated current
of the motor)
6: Output voltage (relative to 1.5 times the rated
voltage of the VFD)
7: Output power (relative to twice the rated power of
the motor)
8: Set torque value (relative to twice the rated torque
of the motor)
9: Output torque (relative to twice the rated torque of
the motor)
10: AI1 input value
11: AI2 input value
0
○
P06.15
AO2 output
0
○
P06.16
HDO
high-speed
pulse output
0
○
Summary of Contents for GD310-011P-4-UL
Page 1: ......
Page 269: ...6 6 0 0 1 0 0 3 9 3 ...