GD310-UL series VFD
Function parameter
-56-
Function
code
Name
Description
Default
value
Modify
P03.11
Torque setting
method
This parameter is used to enable the torque control
mode, and set the torque.
0: Torque control is invalid
1: Keypad setting torque (P03.12)
2: Analog AI1 setting torque
3: Analog AI2 setting torque
4: Analog AI3 setting torque
5: Pulse frequency HDI setting torque
6: Multi-step torque setting
7: MODBUS communication setting torque
8: PROFIBUS/CANopen communication setting
torque
9: Ethernet communication setting torque
10: Reserved
Note
: For setting methods 2
–6, 100% corresponds to
three times of the rated current of the motor.
0
○
P03.12
Keypad setting
torque
Setting range: -300.0%
–300.0% (rated motor
current)
50.0%
○
P03.13
Torque
reference filter
time
0.000
–10.000s
0.010s
○
P03.14
Upper
frequency of
forward
rotation in
vector control
0: Keypad (P03.16 sets P03.14, P03.17 sets P03.15)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDI setting upper-limit frequency
5: Multi-step setting upper-limit frequency
6: MODBUS communication setting upper-limit
frequency
7: PROFIBUS/CANopen communication setting
upper-limit frequency
8: Ethernet communication setting upper-limit
frequency
9: Reserved
Note
: For setting methods 1
–9, 100% corresponds to
the maximum frequency.
0
○
P03.15
Upper
frequency of
reverse
rotation in
vector control
0
○
P03.16
Keypad setting
for upper
frequency of
forward
rotation
This function is used to set the upper limit of the
frequency. P03.16 sets the value of P03.14; P03.17
sets the value of P03.15.
Setting range: 0.00 Hz
–P00.03 (max output
60.00Hz
○