Control long vibration
If the vibration periods are longer than the set value of integral time (Ti), it is necessary to prolong the
integral time (Ti) to control the vibration for the strong integration.
调整前
调整后
响应
时间
t
调整前
调整后
响应
时间
t
Before adjustment
After adjustment
Time
Response
调整前
调整后
响应
时间
t
Control short vibration
Short vibration period and the same set value with the derivative time (Td) mean that the derivative
time is strong. Shortening the derivative time (Td) can control the vibration. When setting the
derivative time as 0.00 (namely no derivation control) is useless to control the vibration, decrease the
gain.
调整前
调整后
响应
时间
t
调整前
调整后
响应
时间
t
调整前
调整后
时间
t
响应
Before adjustment
After adjustment
Response
Time
Related parameters list:
Function
code
Name
Description
Default
value
P09.00
PID reference source
0: Keypad (P09.01)
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed set
0