GD310-UL series VFD
Function parameter
-94-
Function
code
Name
Description
Default
value
Modify
P10.20
Multi-step
speed 9
When terminal 1, terminal 2, terminal 3, terminal
4=OFF, the frequency input manner is selected via
code P00.06 or P00.07. When terminal 1, terminal 2,
terminal 3, terminal 4
aren’t off, it runs at multi-step
which takes precedence of keypad, analog value,
high-speed pulse, PLC, communication frequency
input.
The relationship between terminal 1, terminal 2,
terminal 3, terminal 4 and multi-step speed is as
following:
Terminal 1 OFF ON OFF ON OFF ON OFF ON
Terminal 2 OFF OFF ON ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 OFF OFF OFF OFF OFF OFF OFF OFF
Step
0
1
2
3
4
5
6
7
Terminal 1 OFF ON OFF ON OFF ON OFF ON
Terminal 2 OFF OFF ON ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 ON ON ON ON ON ON ON ON
Step
8
9
10
11
12
13
14
15
0.0%
○
P10.21
Running time
of step 9
0.0s
○
P10.22
Multi-step
speed 10
0.0%
○
P10.23
Running time
of step 10
0.0s
○
P10.24
Multi-step
speed 11
0.0%
○
P10.25
Running time
of step 11
0.0s
○
P10.26
Multi-step
speed 12
0.0%
○
P10.27
Running time
of step 12
0.0s
○
P10.28
Multi-step
speed 13
0.0%
○
P10.29
Running time
of step 13
0.0s
○
P10.30
Multi-step
speed 14
0.0%
○
P10.31
Running time
of step 14
0.0s
○
P10.32
Multi-step
speed 15
0.0%
○
P10.33
Running time
of step 15
0.0s
○
P10.34
Simple PLC
0
–7 step
ACC/DEC
time
Below is the detailed instruction:
Function
code
Binary bit
Step
ACC/
DEC 0
ACC/
DEC 1
ACC/
DEC 2
ACC/
DEC 3
P10.34
BIT1
BIT0
0
00
01
10
11
BIT3
BIT2
1
00
01
10
11
BIT5
BIT4
2
00
01
10
11
BIT7
BIT6
3
00
01
10
11
BIT9
BIT8
4
00
01
10
11
BIT11 BIT10
5
00
01
10
11
BIT13 BIT12
6
00
01
10
11
BIT15 BIT14
7
00
01
10
11
0x0000
○
P10.35
Simple PLC
8
–15 step
ACC/DEC
time
0x0000
○