GD310-UL series VFD
Function parameter
-104-
Function
code
Name
Description
Default
value
Modify
of M is. When M =116%, the fault will be reported
after 1 hour, when M =200%, the fault will be
reported after 1 minute, when M>=400%, the fault
will be reported instantly.
Setting range: 20.0%
–120.0%
P12.28
Correction
coefficient of
motor 2 power
Correct the power displaying of motor 2.
Only impact the displaying value other than the
control performance of the VFD.
Setting range: 0.00
–3.00
1.00
○
P12.29
Parameter
display of
motor 2
0: Display according to the motor type: only the
parameters relative to the current motor type are
displayed for the convenient for the customers in this
mode.
1: All parameters are displayed: all parameters are
displayed in this mode.
0
○
P13 Group Synchronous motor control
Function
code
Name
Description
Default
value
Modify
P13.00
Reduction
coefficient of
source current
0.0
–100.0%
80.0%
◎
P13.01
Original pole
test mode
0: No test
1: High-frequency superposition (reserved)
2: Pulse superposition
0
◎
P13.02
Source current
1
Source current is the positioning current of the
magnetic pole position. Source current 1 is valid
under the frequency point of current shifting.
Increasing the value can raise the starting torque.
Setting range: 0.0%
–100.0% (rated current of the
motor)
20.0%
○