GD310-UL series VFD
Function parameter
-45-
Function
code
Name
Description
Default
value
Modify
When the frequency used exceeds the default carrier
frequency, the VFD needs to derate according to the
detailed information of Appendix B.
Setting range: 1.0
–15.0kHz
P00.15
Motor
parameter
autotuning
0: No operation
1: Rotating autotuning
Comprehensive motor parameter autotune
It is recommended to use Rotating autotuning when
high control accuracy is needed.
2: Static autotuning 1 (autotune totally); It is suitable
in the cases when the motor cannot de-couple from
the load. The autotuning for the motor parameter will
impact the control accuracy.
3: Static autotuning 2 (autotune part parameters);
when the current motor is motor 1, autotune P02.06,
P02.07, P02.08; and when the current motor is motor
2, autotune P12.06, P12.07, P12.08.
0
◎
P00.16
AVR function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can cancel
the impact on the output voltage of the VFD because
of the bus voltage fluctuation.
1
○
P00.17
VFD
type
0: G type, for the constant torque load of rated
parameters
1: P type, for the variable torque load of rated
parameters (fans and waters pumps)
The VFDs can use G/P type, the available motor
power of G type is small one power file than that of P
type.
0
◎
P00.18
Function
restore
parameter
0: No operation
1: Restore the default value
2: Cancel the fault record
Note
: The function code will restore to 0 after
finishing the operation of the selected function code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0
◎
Summary of Contents for GD310-011P-4-UL
Page 1: ......
Page 269: ...6 6 0 0 1 0 0 3 9 3 ...