EonStor DS S12/S16/S24 Series Hardware Manual
Airflow Concern:
Once you are notified that a cooling module has failed, it
should be replaced as soon as possible. A failed module should only be
removed from the system when you have a replacement module
immediately available.
To replace the cooling module:
Step 1.
Snatch the retention latches towards the center, and then pull
the cooling module out of the chassis
.
Removing a Cooling Module
Step 2.
Install the replacement module by pushing it into the
module bay.
When fully inserted, the retention latches will hold
the module in place.
Step 3.
A firmware event will prompt shortly afterwards stating that the
cooling module is back online. The LEDs on the replacement module should
not be lit when installed
.
5.5.3
For S24 series
Detecting a failed cooling module:
If a cooling module fails, system
firmware and SANWatch manager will deliver warning events. The LEDs
located on the cooling module will light red and an audible alarm will
be
triggered.
Airflow Concern:
Once you are notified that a cooling module has failed, it
should be replaced as soon as possible. A failed module should only be
removed from the system when you have a replacement module
immediately available.
143