UA-5200 Series User Manual V4.3 ICP DAS
77
[
Module Content Setting
] page can set up the module and the Modbus address
mapping table:
Module Content Setting
No.
The module number in the module list (Not editable here)
Module Name
Give a name, e.g. model number or name. Default: Name.
Slave ID
Set the module Slave ID of the UA-5200. (Range: 1 ~ 247)
Timeout
Set the timeout value for the module. Default: 500 ms
Modbus Mapping Table Setting
Data Model
System provides 4 Modbus data models
“01” ~ “04” for mapping to address of
DO, DI, AO and AI. (ex. 01: DO
channels, 02: DI, 03: AO, 04: AI)
Start Address
The start address of the Modbus command.
Note:
the address of
UA controller is start from 0, even if some modules are start from 1,
here it needs to set follow the UA series to start from 0.
Data Number
The number of the Modbus address. Need to give enough number
for the DO, DI, AO, AI channels of the module. Default: 1.
Type
This item only when the data model is 03 or 04. Choose the
suitable data type: 16-bit Short, 16-bit Unsigned Short, 32-bit Long,
32-bit Unsigned Long, 32-bit Float, 64-bit Double.
Create Tables
Click [Add] button, it will add a table in the Modbus mapping table.
Summary of Contents for UA-5200 Series
Page 13: ...UA 5200 Series User Manual V4 3 ICP DAS 13 1 5 Appearance UA 5231...
Page 14: ...UA 5200 Series User Manual V4 3 ICP DAS 14 UA 5231M...
Page 15: ...UA 5200 Series User Manual V4 3 ICP DAS 15 UA 5231M 3GWA 4GE 4GC...
Page 225: ...UA 5200 Series User Manual V4 3 ICP DAS 225 The LINE APP messages received on the mobile phone...