UA-5200 Series User Manual V4.3 ICP DAS
120
Condition Trigger Descriptions:
The condition trigger method will different depending on the attribute of the selected
variable and the trigger will be different. There are two operation styles:
DIO
and
AIO
.
(A)
If select
DIO
variable
, then Condition is
“Status Change”. When detecting the status is
changed, it will trigger the event and send the assigned message. (Below is a switch
detecting example.)
DIO Trigger
: (Detect per 500 ms)
1. Detect initial switch status "Off" (status = 0)
2. Detect "Off" (status = 0, status no change), no trigger
3. Detect "On" (status = 1, status changed),
trigger
a message notification
4. Detect "On" (status = 1, status no change), no trigger
5. Detect "Off" (status = 0, status changed),
trigger
a message notification
On/Off
Time (ms)
3. Trigger
5. Trigger
Summary of Contents for UA-5200 Series
Page 13: ...UA 5200 Series User Manual V4 3 ICP DAS 13 1 5 Appearance UA 5231...
Page 14: ...UA 5200 Series User Manual V4 3 ICP DAS 14 UA 5231M...
Page 15: ...UA 5200 Series User Manual V4 3 ICP DAS 15 UA 5231M 3GWA 4GE 4GC...
Page 225: ...UA 5200 Series User Manual V4 3 ICP DAS 225 The LINE APP messages received on the mobile phone...