UA-5200 Series User Manual V4.3 ICP DAS
210
12. Factory Setting Recovering and Middleware
Updating
This chapter will introduce the settings by hardware Rotary Switch, including
“Factory
Setting Recovering
” and “Middleware Updating” that supported since Version 1.0.0.3.
12.1. Recovering to Factory Setting (Rotary Switch: 8)
Turn the Rotary Switch of UA-5200 series to
“8” can recover to the factory setting. Before
that, first to connect the UA controller via a network cable to a PC or a Switch.
The steps:
1. After network connection, power off the UA-5200 hardware, and turn the Rotary
Switch to
“8”.
2. Reboot the UA-5200 and wait a long buzzer sound that means of doing the recovering.
3. Wait about 3 minutes until
2
long buzzer sounds, and then turn the Rotary Switch to
“
0
”.
Note
: If the buzzer makes
4
short beeps, it means the network is not connected
properly. Please check the network cable again.
4. Reboot the UA-5200 again, and the system will recover to the factory settings.
Factory Default Settings of UA-5200
Network
IP
192.168.255.1
Assign UA-5200 a new IP
setting according to your
case.
Netmask
255.255.0.0
Gateway
192.168.1.1
OS
Account
Username
root
After login, change your
password ASAP. (Refer to
Section 5.4
)
Password
icpdas
Web UI
Account
Username
root
Password
root
Summary of Contents for UA-5200 Series
Page 13: ...UA 5200 Series User Manual V4 3 ICP DAS 13 1 5 Appearance UA 5231...
Page 14: ...UA 5200 Series User Manual V4 3 ICP DAS 14 UA 5231M...
Page 15: ...UA 5200 Series User Manual V4 3 ICP DAS 15 UA 5231M 3GWA 4GE 4GC...
Page 225: ...UA 5200 Series User Manual V4 3 ICP DAS 225 The LINE APP messages received on the mobile phone...