Internal Event:
No
Severity:
Info
Alert Category:
System - Other
Serviceable:
No
CIM Information: Prefix:
PLAT and
ID:
0372
SNMP Trap ID:
Automatically notify Support:
No
User response:
No action; information only.
806f0308-0a01ffff
[PowerSupplyElementName] has
lost input. (Power Supply 1)
Explanation:
This message is for the use case when
an implementation has detected a Power Supply that
has input that has been lost.
Internal Event:
No
Severity:
Info
Alert Category:
System - Other
Serviceable:
No
CIM Information: Prefix:
PLAT and
ID:
0100
SNMP Trap ID:
Automatically notify Support:
No
User response:
1.
Reconnect the power cords.
2.
Check power supply n LED.
3.
See Power-supply LEDs for more information. (n =
power supply number)
806f0308-0a02ffff
[PowerSupplyElementName] has
lost input. (Power Supply 2)
Explanation:
This message is for the use case when
an implementation has detected a Power Supply that
has input that has been lost.
Internal Event:
No
Severity:
Info
Alert Category:
System - Other
Serviceable:
No
CIM Information: Prefix:
PLAT and
ID:
0100
SNMP Trap ID:
Automatically notify Support:
No
User response:
1.
Reconnect the power cords.
2.
Check power supply n LED.
3.
See Power-supply LEDs for more information. (n =
power supply number)
806f030c-2001ffff
Scrub Failure for
[PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
(DIMM 1)
Explanation:
This message is for the use case when
an implementation has detected a Memory Scrub
failure.
Internal Event:
No
Severity:
Error
Alert Category:
Critical - Memory
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0136
SNMP Trap ID:
41
Automatically notify Support:
No
User response:
Note: Each time you install or remove
a DIMM, you must disconnect the server from the power
source; then, wait 10 seconds before restarting the
server.
1.
Check the IBM support website for an applicable
retain tip or firmware update that applies to this
memory error.
2.
Manually re-enable all affected DIMMs.
3.
Swap the affected DIMMs (as indicated by the error
LEDs on the system board or the event logs) to a
different memory channel or microprocessor.
4.
If the problem follows the DIMM, replace the failing
DIMM.
5.
(Trained technician only) If the problem occurs on
the same DIMM connector, check the DIMM
connector. If the connector contains any foreign
material or is damaged, replace the system board.
6.
(Trained technician only) Remove the affected
microprocessor and check the microprocessor
socket pins for any damaged pins. If a damage is
found, replace the system board.
7.
(Trained technician only) Replace the affected
microprocessor.
806f030c-2002ffff
Scrub Failure for
[PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
(DIMM 2)
Explanation:
This message is for the use case when
an implementation has detected a Memory Scrub
failure.
Internal Event:
No
Severity:
Error
Alert Category:
Critical - Memory
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0136
806f0308-0a01ffff • 806f030c-2002ffff
Chapter 3. Diagnostics
89
Summary of Contents for System x iDataPlex dx360 M4 7912
Page 1: ...System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 22: ...4 System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 278: ...260 System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 292: ...274 System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 392: ...374 System x iDataPlex dx360 M4 Types 7912 and 7913 Problem Determination and Service Guide...
Page 399: ......
Page 400: ...Part Number 46W8218 Printed in USA 1P P N 46W8218...