022 (continued)
¹
Switch to OFF all the units controlled by this fuse.
¹
Exchange the defective fuse.
¹
Switch ON all the units controlled by this fuse.
Is the fuse blown again?
Yes No
023
Problem solved go to Chapter 6, “CE Leaving Procedure” on
page 6-1.
024
Suspect a power problem in a unit powered through the ac outlet distribution
box.
¹
Switch to OFF all the units controlled by this fuse.
¹
Exchange the fuse.
¹
Switch one by one the units controlled by this fuse to identify the unit
which has a problem.
¹
Once you have identified the faulty unit continue with Step 032 on
page 2-6.
025
Suspect the ac wall socket.
026
Check the corresponding fuse.
Is the fuse OK?
Yes No
027
¹
Switch to OFF the defective unit controlled by this fuse.
¹
Exchange the defective fuse.
¹
Switch ON the unit controlled by this fuse.
Is the fuse blown again?
Yes No
028
Problem solved go to Chapter 6, “CE Leaving Procedure” on
page 6-1.
029
Go to Step 032 on page 2-6
Chapter 2. Service Processor Problem Determination
2-5
Summary of Contents for 3745 Series
Page 2: ......
Page 10: ...viii 3745 XXA viii 3746 9X0 6563 SPIM...
Page 20: ...xviii 3745 XXA xviii 3746 9X0 6563 SPIM...
Page 24: ...xxii 3745 XXA xxii 3746 9X0 6563 SPIM...
Page 74: ...1 50 3745 XXA 1 50 3746 9X0 6563 SPIM...
Page 170: ...5 22 3745 XXA 5 22 3746 9X0 6563 SPIM...
Page 172: ...c If you have a problem call your support for assistance 6 2 3745 XXA 6 2 3746 9X0 6563 SPIM...
Page 182: ...A 10 3745 XXA A 10 3746 9X0 6563 SPIM...
Page 183: ...Appendix A Safety Information A 11...
Page 190: ...A 18 3745 XXA A 18 3746 9X0 6563 SPIM...
Page 200: ...C 6 3745 XXA C 6 3746 9X0 6563 SPIM...
Page 204: ...E 2 3745 XXA E 2 3746 9X0 6563 SPIM...
Page 243: ...Appendix I Service Processor Part Numbers Copyright IBM Corp 1999 I 1...
Page 244: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 I 2 3745 XXA I 2 3746 9X0 6563 SPIM...
Page 246: ...I 4 3745 XXA I 4 3746 9X0 6563 SPIM...
Page 269: ......
Page 270: ...Part Number 10K8590 Printed in U S A 10K8590 SY27 0393 00...