Part 1 Specification
<Reading of Response Command Area>
Send a register read (FC = 03H) query.
Sent Query:
3F03F702000512A3
Received Response: 3F030A 1040 000A 27100000 0000 2E8A
Position data
The position data (2710H) written to the position table in [1] has been
read.
Caution
Each gateway command must be cleared after use.
z
Positioning Band Read Query
Field name
RTU mode data
(8 bits)
Data length
(bytes)
Remarks
Header None
-
Slave address
3F H
1
Fixed.
Function code
10 H
1
Starting address
(upper)
F6 H
Starting address
(lower)
02 H
2
Initial request command register address of axis
(0)
Number of registers
(upper)
00 H
Number of registers
(lower)
05 H
2
The number of registers is 5.
Bytes
0A H
1
Number of registers x 2 = 10 (0AH)
New data 1
(upper)
10 H
New data 1
(lower)
41 H
1 each for upper
and lower words
2
Request command (read positioning band)
New data 2
(upper)
00 H
New data 2
(lower)
0A H
1 each for upper
and lower words
2
Data 0: Position No. 10 is specified.
New data 3
(upper)
00 H
New data 3
(lower)
00 H
1 each for upper
and lower words
2
Data 1: 0
New data 4
(upper)
00 H
New data 4
(upper)
00 H
1 each for upper
and lower words
2
Data 2: 0
New data 5
(upper)
00 H
New data 5
(upper)
00 H
1 each for upper
and lower words
2
Data 3: An axis number is specified (axis 0).
Error check
(CRC)
16 bits
2
Based on calculation result (93D6)
Trailer None
-
Total bytes
19
Sent Query:
3F10F60200050A 1041 000A 00000000
0000 9D36
Received Response: 3F10F6020005969C