Indicator
Color
Status
Description
Off
The bypass software is being upgraded.
Alarm
indicator
Yellow Steady
on
A minor alarm is generated for the bypass.
Off
There is no minor alarm for the bypass, or the
software is being upgraded.
Fault
indicator
Red
Steady
on
A critical alarm is generated for the bypass.
Off
There is no critical alarm for the bypass, or
the software is being upgraded.
Functions
The bypass module supplies power in the following cases:
The UPS is set to ECO mode and the bypass voltage is within the specified range.
The power module overload exceeds the time limit.
Both the active and standby ECMs are abnormal.
The system fails to run properly.
The power supply is switched to the bypass manually.
Specifications
●
Dimensions (H x W x D): 130 mm x 420 mm x 500 mm
●
Weight: 19 kg
●
Rated output capacity: 200 kVA
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
2 Overview
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
27