Port
Connection
Method
Bolt
Specifications
Bolt Hole
Diameter
Bolt Length
Torque
Battery
input
Crimped OT
terminals
M12
13 mm
35 mm
46 N·m
Output
Crimped OT
terminals
M10
11 mm
30 mm
26 N·m
PE
Crimped OT
terminals
M10
11 mm
30 mm
26 N·m
Table 3-4 Recommended upstream input and downstream output circuit breakers
UPS Capacity
Component
Specifications
a
30 kVA
Mains input circuit
breaker
63 A/3P
Bypass input circuit
breaker
63 A/3P
Downstream output
circuit breaker
63 A/3P
60 kVA
Mains input circuit
breaker
125 A/3P
Bypass input circuit
breaker
125 A/3P
Downstream output
circuit breaker
125 A/3P
90 kVA
Mains input circuit
breaker
200 A/3P
Bypass input circuit
breaker
200 A/3P
Downstream output
circuit breaker
200 A/3P
120 kVA
Mains input circuit
breaker
250 A/3P
Bypass input circuit
breaker
250 A/3P
Downstream output
circuit breaker
250 A/3P
a: recommended when the short-circuit current where the switch is located is
less than 36 kA
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
3 Installation
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
51